2.5 Electronic trip unit ETU600
3WA1 air circuit breaker
108 Equipment Manual, 02/2023, 92310000002-06
Technical specifications and connection
The connection is made at the secondary disconnect terminal system of the 3WA circuit
breaker.
Digital input ETU-IN
Connection
X8-5 and X8-6
Number of inputs
1
SELV/PELV suitable
Rated voltage
24 V DC ±20%
Voltage value for reliable detection of a "1 signal":
15 V DC
Current consumption at signal voltage of >15 V DC
< 10 mA
Minimum signal duration
100 ms
Floating output ETU-OUT
Connection
X8-7 and X8-8
Number of semiconductor relay outputs
1
Contact
Normally open contact
Rated voltage
24 V DC ±20%
Maximum switching current
0.1 A at 24 V DC
Maximum continuous current
0.1 A at 24 V DC
The digital input is designed for a control supply voltage of 24 V DC.
No polarity is specified at the DI ETU.0 and DI ETU.1 input terminals.
The digital outputs DO ETU.0 and DO ETU.1 are designed for 24 V DC and as a
normally open contact (NO).
If the power to be switched exceeds the breaking capacity of the output, a suitable
coupling relay must be used.