Description
2.8 Communication and system connection
3WA1 air circuit breaker
Equipment Manual, 02/2023, 92310000002-06
165
• Updating the firmware of the communications module via the SENTRON powerconfig
configuration software
• Resetting the settings to factory settings with PROFINET
Exceptions
Exceptions are the following modifications and actions that are also permitted in write-
protected mode:
• Setting/modifying the system time
• Modifying the free texts (comment, plant designation)
• Resetting the min./max. values
• Resetting the settings to factory settings with function button S1
Remote Switching Protection
Remote Switching Protection (RSP) prevents the opening/closing of the circuit breaker
via the communications interface by means of an open/close command. Remote
Switching Protection uses two terminals on the X61 connector. It is connected to the
communications module with role A and is then effective for communications module A
and optionally also for a second communications module B.
Remote Switching Protection is active by default and must be deliberately deactivated.
The connection (RSP) must be bridged for deactivation.
Temporary activation/deactivation of Remote Switching Protection
Permanent deactivation of Remote Switching Protection
Permanent activation of Remote Switching Protection