2.8 Communication and system connection
3WA1 air circuit breaker
Equipment Manual, 02/2023, 92310000002-06
165
Updating the firmware of the communications module via the SENTRON powerconfig
configuration software
Resetting the settings to factory settings with PROFINET
Exceptions
Exceptions are the following modifications and actions that are also permitted in write-
protected mode:
Setting/modifying the system time
Modifying the free texts (comment, plant designation)
Resetting the min./max. values
Resetting the settings to factory settings with function button S1
Remote Switching Protection
Remote Switching Protection (RSP) prevents the opening/closing of the circuit breaker
via the communications interface by means of an open/close command. Remote
Switching Protection uses two terminals on the X61 connector. It is connected to the
communications module with role A and is then effective for communications module A
and optionally also for a second communications module B.
Remote Switching Protection is active by default and must be deliberately deactivated.
The connection (RSP) must be bridged for deactivation.
(1)
Temporary activation/deactivation of Remote Switching Protection
(2)
Permanent deactivation of Remote Switching Protection
(3)
Permanent activation of Remote Switching Protection