2.10 Zone-selective interlocking ZSI
3WA1 air circuit breaker
192 Equipment Manual, 02/2023, 92310000002-06
Fault scenario A:
The -Q4, -Q3 and -Q1 circuit breakers detect the short-circuit. Via the ZSI system,
circuit breaker -Q3 is informed of the pick-up of -Q4 and circuit breaker -Q1 is
informed of the excitation of -Q3. This prevents tripping of the circuit breakers -Q3
and -Q1 with delay t
ZSI
.
The -Q4 circuit breaker does not receive any pick-up information from a downstream
circuit breaker at the ZSI interface port A. Therefore, the -Q4 circuit breaker trips
after the adjustable delay t
ZSI
for the short-time-delayed short-circuit protection.
If the fault current cannot be switched off by the -Q4 circuit breaker, tripping of -Q3
and -Q1 as back-up protection takes place in each case after the parameterized delay
time t
sd
.
The fault current does not flow through the -Q2 and -Q5 circuit breakers and they are
therefore not considered in more detail.
Fault scenario B:
The -Q3 and -Q1 circuit breakers detect the short-circuit. Via the ZSI system, circuit
breaker -Q1 is informed of the pick-up of -Q3. This prevents tripping of -Q1 after the
delay t
ZSI
.
The -Q3 circuit breaker does not receive any pick-up information from a downstream
circuit breaker at its ZSI interface port A. Therefore, the -Q3 circuit breaker trips after
the adjustable delay t
ZSI
for the short-time-delayed short-circuit protection.
If the fault current cannot be switched off by the -Q3 circuit breaker, tripping of -Q1
as back-up protection takes place after its delay time t
sd
.
Fault scenario C:
The -Q1 circuit breaker detects the short-circuit and does not receive any information
about the pick-up of a downstream circuit breaker.
-Q1 therefore trips after the delay t
ZSI
.
In this example, it can be seen that the load on the power distribution system in the
event of a short-circuit is significantly reduced by the ZSI system.
The following table lists the delays of the ETU600 electronic trip unit until the trip
command for the three fault cases.
Fault situation
Without ZSI system
With ZSI system
A: Tripping -Q4
0.265 s
0.04 s
B: Tripping -Q3
0.330 s
0.04 s
C: tripping -Q1
0.400 s
0.04 s