3.2 Using the 3WA circuit breaker for motor protection
3WA1 air circuit breaker
Equipment Manual, 02/2023, 92310000002-06
205
Trip classes T
C
Trip class T
C
specifies the tripping time T
p
with a symmetrical 3-pole load, starting from
the cold state, with 7.2 times the set current I
r
according to IEC EN 60947 4-1.
Trip class T
C
Tripping time T
p
5
0.5 s < T
p
< 5 s
10A
2 s < T
p
< 10 s
10
4 s < T
p
< 10 s
20
6 s < T
p
< 20 s
30
9 s < T
p
< 30 s
Tripping time t
r
of the 3WA circuit breaker's overload protection LT is defined at 6 times
the current setting value I
r
and can be set in the range from 0.5 to 30 s.
For overload protection LT with I
2
t characteristic, tripping time t
r
can be assigned to the
tripping time T
p
and a trip class T
c
.
Tripping time t
r
Tripping time T
p
Trip class T
c
at 6 times the current setting
value
at 7.2 times the current
setting value
5 10A 10 20 30
0.5 s
0.3 s
--
--
--
--
--
1 s
0.7 s
--
--
--
--
2 s
1.4 s
--
--
--
--
5 s
3.5 s
--
--
--
8 s
5.6 s
--
--
--
10 s
6.9 s
--
--
--
14 s
9.7 s
--
--
17 s
11.8 s
--
--
--
21 s
14.6 s
--
--
--
--
25 s
17.4 s
--
--
--
--
30 s
20.8 s
--
--
--
--