EasyManua.ls Logo

Siemens SENTRON 3WA1 - Page 255

Siemens SENTRON 3WA1
576 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Accessories
4.3 Control and signaling accessories
3WA1 air circuit breaker
Equipment Manual, 02/2023, 92310000002-06
253
Max. breaking capacity (resistive)
90 W at 30 V DC
1.385 VA at 277 V AC
Switching frequency
500,000 cycles at 1 A, 250 V AC, ohmic load
Connectable conductor cross-sections
Design of electrical connection
Removable / push-in connection terminal
Solid
0.2 … 1.5 mm
2
Finely stranded / with end sleeve
0.25 … 1.5 mm
2
Finely stranded
0.2 … 2.5 mm
2
For solid AWG cable
AWG24 … AWG16
Electromagnetic compatibility
Conducted or radiated emissions
EN 60947-1
EN 60947-2 (CISPR 11 (Group 1, Class B))
FCC Class A
Shipbuilding requirements
Immunity in industrial environment
EN 60947-1
EN 60947-2
Shipbuilding requirements
Ambient conditions
Operation
40 … +70 °C
Transport and storage
40 … +80 °C
Degree of pollution
3
The digital inputs are designed for a control supply voltage of 24 V DC.
No polarity is specified at the DI x.0 and DI x.1 input terminals. Both inputs are
isolated and can be fed from independent sources.
The three outputs of the digital input/output module IOM230 are normally open
contacts (NO).
If the power to be switched exceeds the breaking capacity of the output, a suitable
coupling relay must be used.