EasyManua.ls Logo

Siemens SENTRON 3WA1 - Page 265

Siemens SENTRON 3WA1
576 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Accessories
4.3 Control and signaling accessories
3WA1 air circuit breaker
Equipment Manual, 02/2023, 92310000002-06
263
Supply
Input voltage
24 V DC
110 … 240 V AC
Current consumption
100 mA at 24 V DC for 100 ms
20 mA at 230 V AC for 100 ms
Current peaks (inrush) <1 A for 100 µs possible
After 100 ms <10 mA
Required pulse length of input voltage
100 ms
Recommended pulse length of input voltage
200 ms … 5 s
Reset time
Min. 5 s
Delay Δt of output pulse
Max. 50 ms
Maximum number of control cycles per hour
60
Connection elements and terminals
Design of electrical connection
Removable/push-in connection terminal
Connectable conductor cross-sections
Solid: 1.5 mm
2
Finely stranded / with end sleeve 0.75 mm
2
For solid AWG cable 1 x AWG16,
2 x AWG 19/20
Electromagnetic compatibility
Conducted or radiated emissions
EN 60947-1
EN 60947-2 (CISPR 11 (Group 1, Class B))
FCC Class A
Shipbuilding requirements
Immunity in industrial environment
EN 60947-1
EN 60947-2
Shipbuilding requirements
Ambient conditions
Operation
40 … +70 °C
Transport and storage
40 … +80 °C
Degree of pollution
3
Degree of protection
Degree of protection acc. to IEC 60529
IP20

Table of Contents