Inspection and maintenance
5.5 Preparing for maintenance work
3WA1 air circuit breaker
Equipment Manual, 02/2023, 92310000002-06
401
2. Open the circuit breaker and discharge the stored-energy spring.
Press O / OPEN.
Isolate the auxiliary circuits by unplugging the manual connectors.
Press I / CLOSE.
A charged stored-energy spring is discharged.
Press O / OPEN.
Ensure that the switch position indicator shows OPEN.
The circuit breaker is open.
Ensure that the switch position indicator shows DISCHARGED.
The stored-energy spring is discharged.