Technical specifications
6.3 Technical specifications of 3WA circuit breakers
3WA1 air circuit breaker
Equipment Manual, 02/2023, 92310000002-06
493
3WA11
AC
Endurance (operating cycles)
Breaking capacity N
Mechanical
Without maintenance
15000
15000
15000
15000
15000
15000
15000
With maintenance
4)
30000
30000
30000
30000
30000
30000
30000
Electrical
Without maintenance 690 V
10000
10000
10000
10000
10000
7500
5000
With maintenance
4)
30000
30000
30000
30000
30000
30000
30000
Breaking capacity S
Mechanical
Without maintenance
15000
15000
15000
15000
15000
15000
15000
With maintenance
4)
30000
30000
30000
30000
30000
30000
30000
Electrical
Without maintenance 690 V
10000
10000
10000
10000
10000
7500
5000
With maintenance
4)
30000
30000
30000
30000
30000
30000
30000
Breaking capacity M
5)
Mechanical
Without maintenance
10000
10000
10000
10000
10000
10000
10000
With maintenance
4)
15000
15000
15000
15000
15000
15000
15000
Electrical
Without maintenance 690 V
10000
10000
10000
10000
10000
7500
5000
With maintenance
4)
15000
15000
15000
15000
15000
15000
15000
Breaking capacity E
5)
Mechanical
Without maintenance
10000
10000
10000
10000
10000
10000
10000
With maintenance
4)
15000
15000
15000
15000
15000
15000
15000
Electrical
Without maintenance 690 V
10000
10000
10000
10000
10000
7500
5000
Without maintenance
1000 V
1000
1000
1000
1000
1000
1000
1000
With maintenance
4)
15000
15000
15000
15000
15000
15000
15000
4)
Maintenance means: Replace main contacts and arc chutes (see Chapter Inspection and maintenance
(Page 387))
5)
The main contact elements can only be replaced in the factory.
Switching frequency
6)
Breaking capacity N and S
Electrical
3-pole
45 / h
45 / h
45 / h
45 / h
45 / h
45 / h
45 / h
4-pole
45 / h
45 / h
45 / h
45 / h
45 / h
45 / h
45 / h
Breaking capacity M
Electrical
3-pole
45 / h
45 / h
45 / h
45 / h
45 / h
45 / h
45 / h
4-pole
60 / h
60 / h
60 / h
60 / h
60 / h
60 / h
60 / h
Breaking capacity E
Electrical
≤ 1000 V
3-pole
45 / h
45 / h
45 / h
45 / h
45 / h
45 / h
45 / h
4-pole
60 / h
60 / h
60 / h
60 / h
60 / h
60 / h
60 / h
6)
Minimum interval time between two operations