Integration in power distribution equipment   
7.4 Requirement according to IEC 61439 
  3WA1 air circuit breaker 
536  Equipment Manual, 02/2023, 92310000002-06 
3WA 
instead of 
Are the materials and the material properties of the conductors of each 
circuit of the switchgear and controlgear assembly to be tested the same as 
those of the reference design? 
Are the short-circuit protection devices of each circuit of the switchgear and 
controlgear assembly to be tested equivalent, i.e. same manufacturer and 
same series
1)
 with the same or better current-limiting properties (I
2
t, I
pk
) 
based on information from the device manufacturer, and is their 
arrangement identical to that of the reference design? 
Is the length of the unprotected active conductors according to standard 
IEC 61439-2 of each unprotected circuit of the switchgear and controlgear 
assembly to be tested less than or equal to that of the reference design? 
Switchgear and controlgear assembly with enclosure to be tested: Does the 
reference design also take an enclosure into account during verification 
testing? 
Is the enclosure of the switchgear and controlgear assembly to be tested 
identical in design and type to that of the reference design? Are its 
dimensions at least the same? 
Is the compartment of each circuit of the switchgear and controlgear 
assembly to be tested identical to the mechanical design of the reference 
design? Are their dimensions at least the same? 
1)
  Short-circuit protective devices from the same manufacturer, but from a different series may 
be regarded as equivalent if the device manufacturer confirms that the behavioral properties 
are the same or better in every relevant respect as those of the series used for verification 
(e.g. breaking capacity, current-limiting properties (I
2
t, I
pk
) and critical spacings). 
2)
  The circuit breaker requires no changes provided the rated current and breaking capacity 
•  If you can answer "Yes" to all the points in the checklist, you can replace the 3WL 
circuit breaker with a 3WA circuit breaker without any further verification. 
•  If you answer "No" to one or more of the points in the checklist, you must provide 
further verification with respect to the integrity of the power distribution equipment in 
order to replace the 3WL circuit breaker with a 3WA circuit breaker. 
Note 
Observe the instructions for partitions in Chapter Phase barriers and horizontal partitions 
(Page
 537).