Troubleshooting   
8.3 Troubleshooting for COM150 / COM 190 communications module 
  3WA1 air circuit breaker 
548  Equipment Manual, 02/2023, 92310000002-06 
All LEDs on the communications 
module flash red. 
The communications module has 
detected faults and is not ready for 
operation. 
Reset the communications module to 
the factory settings.  
If the error message persists, replace 
the communications module. 
The communications module cannot 
be addressed via Modbus TCP. 
Access is restricted due to security 
functions. 
Check the security functions. 
Write protection is active. 
Set the slide switch on the 
communications module to the   
position (open padlock). For more 
information, see Chapter Access 