EasyManua.ls Logo

Siemens SENTRON PAC3100 - Page 107

Siemens SENTRON PAC3100
152 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical data
11.1 Technical data
SENTRON PAC3100
Manual, 07/2009, A5E02385159B-01
107
Digital inputs
Number 2
Type Internal power supply
External operating voltage 0 ... 30 V DC (optional)
Contact resistor
"1" signal detection ≤ 1 kΩ
"0" signal detection ≥ 100 kΩ
Input current
"1" signal detection 2.5 … 10 mA
"0" signal detection ≤ 0.5 mA
Digital outputs
Number 2
Type Bidirectional
Design/function Switching output or pulse output
Rated voltage 0 ... 30 V DC, typical 24 V DC
(SELV or PELV supply)
Output current
For signal "1" Depends on the load and the external power
supply
Continuous load ≤ 50 mA (thermal overload protection)
Transient overload ≤ 130 mA for 100 ms
For signal "0" ≤ 0.2 mA
Internal resistance 55 Ω
Overvoltage category CAT I
Pulse output function
Standard for pulse emitter Signal characteristics in accordance with
IEC 62053-31
Adjustable pulse duration 30 … 500 ms
Min. settable time frame 10 ms
Max. switching frequency 17 Hz
Short-circuit protection Yes

Table of Contents