SENTRON PAC3100
Manual, 07/2009, A5E02385159B-01
29
Operation planning
4
Mounting location
The SENTRON PAC3100 device is intended for installation in permanently installed
switching panels within closed rooms.
Conductive panels and doors on control cabinets must be grounded. The doors of the control
cabinet must be connected to the control cabinet using a grounding cable.
Mounting position
The device must be installed vertically.
r
r
Figure 4-1 Mounting position
The preferred direction of viewing is from below at an angle.
Installation space and ventilation
Sufficient clearance must be maintained between the device and neighboring components in
order to comply with the permissible operating temperature. You can find dimension
specifications in the "Dimensional drawings" chapter.
Plan additional space for:
● Ventilation
● Wiring
● RS 485 terminal block and cable infeed on the top of the device
CAUTION
Ensure ventilation
Please ensure that the ventilation slots of the housing are not obstructed. The wiring, cable
feed or other components must not obstruct ventilation.