Commissioning
7.3 Parameterizing the device
SENTRON PAC3100
58 Manual, 07/2009, A5E02385159B-01
Example:
You want to measure using voltage transformers for 1000 V/100 V on a 690 V system.
For this purpose, enter:
1. USE PTs?:
On:
2. PT PRIMARY: 690 V
3. PT SECONDARY: 69 V
Figure 7-7 "VOLTAGE INPUTS" device setting
See also
Measurement using voltage transformers (Page 56)
7.3.2.4 Setting the voltage input
The factory setting for the measuring reference voltage V
ph-ph
is 400 V. At initial startup, the
following steps must be carried out if the available measuring voltage V
ph-ph
deviates from
this.
Procedure
1. In the "SETTINGS" menu, call the "BASIC PARAMETERS" entry.
2. In the "BASIC PARAMETERS" menu, open the "VOLTAGE INPUTS" entry:
<F4>
The display shows the currently valid settings.
3. Go to the "VOLTAGE INPUTS" device setting:
<F2>
or <F3>
Figure 7-8 "VOLTAGE INPUTS" device setting
4. Open edit mode of the "VOLTAGE INPUTS" device setting:
<F4>
5. Set the desired value:
<F2>
and <F3>
6. Accept the value:
<F4>