Loading...
Mounting
5.2 Mounting on the switching panel
SENTRON PAC3100
32 Manual, 07/2009, A5E02385159B-01
5.2 Mounting on the switching panel
5.2.1 Tools
You require the following tools for installation:
Cutting tool for the panel cutout
Screwdriver PH2 cal. ISO 6789
Additional installation tools
Cable clamp for strain relief on the RS 485 connection.
5.2.2 Mounting dimensions
Mounting and clearance dimensions
You can find information on the cutout dimensions, frame dimensions and clearances in the
Chapter "Dimensional drawings".
See also
Dimensional drawings (Page 115)
5.2.3 Installation steps
Proceed as follows to install the SENTRON PAC3100 in the switching panel:
Procedure
1. Cut a hole in the panel measuring 92.0
+0.8
x 92.0
+0.8
mm
2
(if not already available).
2. Discharge any static from your body. Observe the ESD guidelines in the Appendix.
CAUTION
Electrostatic sensitive devices
Discharge your body of any static electricity. Touch the grounded control cabinet, for
example, or a metal part that is connected to the building ground (heater, steel support).