EasyManua.ls Logo

Siemens SENTRON PAC3100 - Digital Outputs; Figure 3-7 Digital Inputs with Switch, Internal Power Supply, and Additional External Power Supply on; Figure 3-8 Energy Pulse Output

Siemens SENTRON PAC3100
152 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Description
3.5 Digital inputs and outputs
SENTRON PAC3100
Manual, 07/2009, A5E02385159B-01
25
Switch with external power supply
In addition to the internal voltage on terminal DIC, and external voltage up to 30 V (typically
24 V) can be applied to terminal DIC.
DIC DI0
DI1
DOC
DO0
DO1
(1) Functional ground terminal
(2) External voltage
Figure 3-7 Digital inputs with switch, internal power supply, and additional external power supply on
terminal DIC
3.5.2 Digital outputs
Functions
The following functions can be assigned to both digital outputs:
Energy pulse output, programmable for active or reactive energy
Switching output for remote control via the RS 485 interface
Energy pulse output
The digital output supplies a number of pulses proportional to one of the following energies:
Active energy import
Active energy export
Reactive energy import
Reactive energy export
Figure 3-8 Energy pulse output

Table of Contents