Commissioning
7.3 Parameterizing the device
SENTRON PAC3100
Manual, 07/2009, A5E02385159B-01
53
7.3 Parameterizing the device
Procedure
To start up the device, you must specify the operating parameters listed below in the device
settings:
Connection type
Voltage
Direct measurement on the system or using voltage transformers
Measuring input voltage in the case of direct measurement on the system
Primary and secondary voltage when measuring using voltage transformers
Current
Primary current
When using the RS 485 interface:
Communication settings
The following settings are also useful:
Language
Phase labels
Password protection
See also
Password management (Page 95)
7.3.1 Setting the language
First, set the language in which the display text is to appear.
The available languages are displayed:
at initial startup,
after resetting to factory settings
English is the default language.
Figure 7-1 Language selection