Appendix
A.2 Modbus RTU
SENTRON PAC3100
138 Manual, 07/2009, A5E02385159B-01
A.2.11 Modbus device information with the function codes 0x03, 0x04 and 0x10
Addressing the device information parameters
You access the following device information parameters block-by-block only, e.g. read from
Offset 64001 27 Register.
NOTICE
Error in the case of inconsistent access to I&M data
Please ensure the start offset and the number of registers are correct when making read
accesses and write accesses. Always read or write the entire block.
Please ensure the start offset and the number of registers are correct when making write
accesses.
If a value consists of several registers, a read command applied in the second register, for
example, will generate an error code. SENTRON PAC will also output an error code if, for
example, a write operation ends in the middle of a multi-register value.
Table A- 17 I&M 0 parameters with the function codes 0x03 and 0x04
Offset Total
registers
Number of
registers per
parameter
Name Format Value range
from ... to
Access
Start offset
64001
[1] Manufacturer's ID unsigned short 42
*)
R
[64002] [10] Order No. Char 20 ASCII R
[64012] [8] Serial number Char 16 ASCII R
[64020] [1] Hardware version unsigned short 0 ... 65535 R
[64021] [2] Firmware version 1 char, 3 unsigned
char
V 0.0.0 ...
V 255.255.255
R
[64023] [1] Counter for changes unsigned short 1 ... 65535 R
[64024] [1] Profile ID unsigned short 3A00 ... F6FF R
[64025] [1] Specific Profile ID unsigned short - R
[64026] [1] Version of the I&M data 2 unsigned char 0.0 ... 255.255 R
[64027]
27
[1] Supported I&M data unsigned short 00 ... FF R
*) 42 stands for Siemens AG
Table A- 18 I&M 1-4 parameters with the function codes 0x03, 0x04 and 0x10
Offset Total
registers
Number of
registers per
parameter
Name Format Value range
from ... to
Access
Start offset
64028
[16] Plant identifier Char 32 ASCII RW
[64044] [11] Location identifier Char 22 ASCII RW
[64055] [8] Installation date Char 16 ASCII RW
[64063] [27] Comment Char 54 ASCII RW
[64090]
89
[27] Signature Char 54 - RW