Parameterizing
9.2 Parameterizing the operator interface
SENTRON PAC3100
88 Manual, 07/2009, A5E02385159B-01
CURRENT DIREC a
CURRENT DIREC b
CURRENT DIREC c
Inverse evaluation of the current flow direction separately for
each phase.
ON/OFF switch:
ON / OFF.
OFF: SENTRON PAC3100 interprets the direction of
current flow in accordance with the wiring.
On: Direction of current flow is inverted.
SENTRON PAC3100 interprets the direction of current
flow opposite to the wiring.
Default value:
OFF
See also
Voltage input (Page 55)
Current input (Page 59)
9.2.5 Power demand
Device settings for acquiring the power demand.
Call: "SETTINGS > POWER DEMAND."
Figure 9-6 "POWER DEMAND" device setting
Power demand
TIME INTERVAL Time interval in minutes
Range: 1 to 60 min.
Default value: 15 min.
SYNC. VIA BUS Synchronization via bus
ON/OFF switch:
ON / OFF.
Default value:
OFF.
See also
Acquisition of power demand (Page 22)