A.1.4 Measured variables without a time stamp with the function codes 0x03 and
0x04
Addr
essing the measured variables without a time stamp
The PAC4220 Power Monitoring Device provides measured variables with or without a time
stamp.
Note
Err
or in t
he case of inconsistent access to measured values
Please ensure the start o󹪜set of the register is correct when making read accesses.
Please ensure the start o󹪜set and the number of registers are correct when making write
accesses.
If a value consists of 2 registers, a read command applied in the second register, for example, will
generate an error code. The PAC4220 will also output an error code if, for example, a write
operation ends in the middle of a multi-register value.
###Information Markus Braun/Thomas Reisinger: Table not yet 󹪝nal. Final t
able
(Datadictionary) will be supplied at a later time###
Table A-2 Measured variables available without a time stamp
O󹪜set Number
of r
egis‐
t
ers
Name Format Unit Value range Access
1 2 VoltageL1‑N Float V R
3 2 VoltageL2‑N Float V R
5 2 VoltageL3‑N Float V R
7 2 VoltageL1‑L2 Float V R
9 2 Voltage L2‑L3 Float V R
11 2 Voltage L3‑L1 Float V R
13 2 CurrentL1 Float A R
15 2 CurrentL2 Float A R
17 2 CurrentL3 Float A R
19 2 Apparent powerL1 Float VA R
21 2 Apparent powerL2 Float VA R
23 2 Apparent powerL3 Float VA R
25 2 Active powerL1 Float W R
27 2 Active powerL2 Float W R
29 2 Active powerL3 Float W R
37 2 Power factorL1 Float - 0…1 R
39 2 Power factorL2 Float 0…1 R
41 2 Power factorL3 Float 0…1 R
43 2 THD voltageL1‑L2 Float % 0…100 R
45 2 THD voltageL2‑L3 Float % 0…100 R
Appendix
A.1Modbus
PAC4220
Equipment Manual, L1V30827278B-01 115