A.1.4 Measured variables without a time stamp with the function codes 0x03 and
0x04
Addr
essing the measured variables without a time stamp
The PAC4220 Power Monitoring Device provides measured variables with or without a time
stamp.
Note
Err
or in t
he case of inconsistent access to measured values
Please ensure the start oset of the register is correct when making read accesses.
Please ensure the start oset and the number of registers are correct when making write
accesses.
If a value consists of 2 registers, a read command applied in the second register, for example, will
generate an error code. The PAC4220 will also output an error code if, for example, a write
operation ends in the middle of a multi-register value.
###Information Markus Braun/Thomas Reisinger: Table not yet nal. Final t
able
(Datadictionary) will be supplied at a later time###
Table A-2 Measured variables available without a time stamp
Oset Number
of r
egis‐
t
ers
Name Format Unit Value range Access
1 2 VoltageL1‑N Float V ‑ R
3 2 VoltageL2‑N Float V ‑ R
5 2 VoltageL3‑N Float V ‑ R
7 2 VoltageL1‑L2 Float V ‑ R
9 2 Voltage L2‑L3 Float V ‑ R
11 2 Voltage L3‑L1 Float V ‑ R
13 2 CurrentL1 Float A ‑ R
15 2 CurrentL2 Float A ‑ R
17 2 CurrentL3 Float A ‑ R
19 2 Apparent powerL1 Float VA ‑ R
21 2 Apparent powerL2 Float VA ‑ R
23 2 Apparent powerL3 Float VA ‑ R
25 2 Active powerL1 Float W ‑ R
27 2 Active powerL2 Float W ‑ R
29 2 Active powerL3 Float W ‑ R
37 2 Power factorL1 Float - 0…1 R
39 2 Power factorL2 Float ‑ 0…1 R
41 2 Power factorL3 Float ‑ 0…1 R
43 2 THD voltageL1‑L2 Float % 0…100 R
45 2 THD voltageL2‑L3 Float % 0…100 R