7.1.6 Display
Selection Range Factory setting
FFT DISPLAY TYPE The device gives you the option of displaying the odd (3rd to
63rd) or all (1s
t to 64th) harmonics on the PAC4220 display.
• 3, 5, 7 ...63: Only odd harmonics
• 2, 3, 4 ... 64: All harmonics
3, 5, 7 ... 63
BACKLIGHT LEVEL Intensity of the backlighting of the LC display.
0 ... 3
3
BACKLIGHT DIMMED Intensity of the backlighting of the LC display.
Se
t
by the device after the display time until dimmed expires.
See "TIME UNTIL DIMMED" eld
0 (switches backlighting o) ... 3
1
TIME UNTIL DIMMED Time after which the device switches the backlighting from
"BA
CKLIGHT LEVEL" to "BACKLIGHT DIMMED".
0min...99min
3min
DEFAULT MENU The menu display number for the main menu can be entered
here.
The device then always starts up with the menu item 1 ...
28 dened here.
1
TIMEOUT The menu display time can be specied her
e. When the speci‐
ed time has elapsed, the device automatically returns to the
dened main menu. 0s (function deactivated)... 3600s
0s
DISPLAY TEST... Screen for testing the functional capability of the display.
• F3: Selection of t
est color
• F4 closes the display.
-
Parameterizing
7.1Parameterizing via the operator interface
PAC4220
Equipment Manual, L1V30827278B-01 85