8.4 Troubleshooting guide
Remedies f
or the resolution of faults
Fault Remedies
Device is not working
Check power supply
Chec
k fuse
Voltage or current measured values are not dis‐
play
ed
Check fuse
Check con󹪝guration
(see Parameterizing the device (Page79))
Voltage values are not plausible
If voltage transformers are available, check the settings and the connec‐
tion of the v
oltage transformers and correct if necessary
Current values are not plausible
Check the settings and the wiring of the current transformer (if present)
and cor
rect if necessary
No communication
Check the communication settings
(incorr
ect IP address, incorrect subnet, incorrect Modbus TCP port or
gateway?)
Check 󹪝rewall, if present
(possibly preventing communication to the Modbus ports)
Power values are incorrect, although voltage
and curr
ent are correctly applied
Check voltages and currents of the phases, if present
Check the polarity of the current transformers
(for incorrect polarity)
Fault indication in the display menu:
"VOID"
The device is defective and cannot be repaired.
If the device fault cannot be remedied by the measures given above, the device is probably
defectiv
e.
More help is available on the internet. (
https://www.siemens.de/lowvoltage/support-request)