5.4 Applying the measuring voltage
The po
wer monitoring device is designed for operation with the following measuring voltages:
Rated voltage
• 57.5/100...400/690V(IEC)
• 57.5/100...347/600V(UL)
NOTICE
Observe limit values
The maximum limits giv
en in t
he technical data or on the rating plate must not be exceeded
even at startup or when testing the device.
Measurement of DC voltage is not possible.
External voltage transformers are required to measure higher voltages than the permissible
rated input voltages.
See also
Applying t
he supply voltage (Page58)
Safety information (Page43)
Commissioning
5.4Applying the measuring voltage
PAC4220
62 Equipment Manual, L1V30827278B-01