Description
2
2.1 Performance features
The P
A
C4220 is a Power Monitoring Device for measuring the basic electrical variables in low-
voltage power distribution. The device is capable of single-phase, two-phase or three-phase
measurement and can be used in 2, 3 or 4-wire TN, TT and IT systems.
The PAC4220 is designed for panel mounting. It is also possible to mount it on a DIN rail
using the DIN rail support brackets available as an option.
Thanks to its large measuring voltage range, the PAC4220 with a wide-voltage power supply
can be connected in any low-voltage system up to a rated line voltage of 690V (max. 600V
for UL). Higher voltages can be measured using voltage transformers.
Either x/1A or x/5A current transformers can be used for measuring current.
The large graphical color display is used to read o all the measured values and to congure
the device.
The integral Ethernet interface or the interface of an expansion module available as an
option can be used for communication, e.g. SENTRON PACRS485 expansion module or
SENTRON PACPROFIBUSDP expansion module or PAC SWITCHED ETHERNET PROFINET
module. The functions of the device can be expanded using other expansion modules
available as options. The PAC4220 has 2 interfaces which can accommodate up to 2 external
expansion modules simultaneously.
Measurement
• Measurement in 2, 3 and 4-wire systems Suitable for TN, TT and IT systems
• Measurement of all relevant electrical variables in a 50/60 Hz AC system
• Measurement of minimum and maximum values of all measured variables
1)
• Calculation of genuine rms values for voltage and current to the 64thharmonic
• 4-quadrant measurement (import and export)
• Averaging of all measured values directly on the device in 2 stages, which are independent
of each other and freely congurable (aggregation)
1)
• Measurement of 1st to 63rdharmonics for voltage and current
• Calculation of the average voltage and current values over all phases
• Zero blind measurement
• High measuring accuracy: for instance, accuracy class 0.2 in accordance with IEC 61557-12
for active energy This means: an accuracy of 0.2% relative to the measured value under
reference conditions
• Measurement of N (neutral) conductor current
2)
PAC4220
Equipment Manual, L1V30827278B-01 15