Oset Number
of regis‐
t
ers
Name Format Unit Value range Access
281 2 Total reactive powerL2(Qtot) Float VAR ‑ R
283 2 Total reactive powerL3(Qtot) Float VAR ‑ R
285 2 Reactive powerL1(Q1) Float VAR ‑ R
287 2 Reactive powerL1(Q1) Float VAR ‑ R
289 2 Reactive powerL1(Q1) Float VAR ‑ R
291 2 Unbalance voltage Float % 0…100 R
293 2 Unbalance current Float % 0…100 R
295 2 Neutral current Float A ‑ R
297 2 Total reactive power (Qtot) Float VAR ‑ R
299 2 Total reactive power (Q1) Float VAR ‑ R
1)
The follo
wing tables contain further details of all the measured variables indicated by this superscript.
2)
You can additionally use the Modbus function code 0x10 on all measured variables indicated by this superscript.
Table A-3 Meaning of the abbreviations in the "Access" column
Abbreviation Meaning
R Read access
W Write access
RW Read and write access
A.1.5 T
ar
i-specic energy values in double format with the function codes 0x03,
0x04, and 0x10
Addressing the tari-specic energy values
Table A-4 Available tari-specic measured variables
Oset Number
of r
egis‐
t
ers
Name Format Unit Value range Access
797 4 Date/time Time stamp ‑ ‑ RW
801 4 Active energy import t
ar
i1 Double Wh Overow1.0e+12 RW
805 4 Active energy import tar
i2 Double Wh Overow1.0e+12 RW
809 4 Active energy export tar
i1 Double Wh Overow1.0e+12 RW
813 4 Active energy export tar
i2 Double Wh Overow1.0e+12 RW
817 4 Reactive energy import tar
i1 Double VARh Overow1.0e+12 RW
821 4 Reactive energy import tar
i2 Double VARh Overow1.0e+12 RW
825 4 Reactive energy export tar
i1 Double VARh Overow1.0e+12 RW
829 4 Reactive energy export tar
i2 Double VARh Overow1.0e+12 RW
Appendix
A.1Modbus
PAC4220
118 Equipment Manual, L1V30827278B-01