A.1.10 Conguration se
ttings with the function codes 0x03, 0x04, and 0x10
Addressing the conguration settings
You can use the Modbus function codes 0x03 and 0x04 for read accesses and 0x10 for write
accesses to all the conguration settings listed below.
Table A-8 Conguration settings
Oset Number
of r
egis‐
t
ers
Name Format Unit Value range Access
49999 2 Rated current display range Unsigned long A 1...99999 RW
50001 2 Connection type Unsigned long - 0= 3P4W RW
1= 3P3W
2= 3P4WB
3= 3P3WB
4= 1P2W
50003 2 Voltage transformer Yes/No Unsigned long - 0= No RW
1= Yes
50005 2 Primary voltage Unsigned long - 1 ...999999V RW
50007 2 Secondary voltage Unsigned long - 1 ... 690V RW
50009 2 Voltage transformer Yes/No? Unsigned long - 1= Yes RW
50011 2 Primary current Unsigned long - 1 ...999999V RW
50013 2 Secondary current Unsigned long - 1A, 5A RW
50017 2 Line frequency Unsigned long - - RW
50019 2 Zero point suppression Float % 0.0…10.0 RW
1)
Subperiods 0 and 1: F
ixed block method; subperiods 0 to 5: Rolling block method