A.1.11 I&M settings
Addr
essing the settings for the I&M data
Table A-9 Settings for the I&M data
O󹪜set Number
of r
egis‐
t
ers
Name Format Unit Applicable MOD‐
BUS function co‐
des
Value range Access
64001 27 PAC4220 I&M 0 data stIM0 -
0x03
0x04
- R(W)
64028
89 PAC4220 I&M1 to I&M4 data stIM14 -
0x03
0x04
0x10
- RW
64117 27 IM Data Module Interface1 stIM0- -
0x03
0x04
- R(W)
64144
27 IM Data Module Interface2 stIM0 -
0x03
0x04
- R(W)
A.1.12 Commands with the function code 0x06
Addr
essing the commands
Table A-10 Commands
O󹪜set Number
of r
egis‐
t
ers
Name Format Applicable
MODBUS func‐
tion codes
Value range Access
60000 1 Reset device to factory set‐
tings
Unsigned
short
0x06 4711 W
60006
1 Switching tari󹪜 U
nsigned
short
0x06 0= On-peak tari󹪜 W
1= O󹪜-peak tari󹪜
60007
1 Acknowledge diagnostics
bits
Unsigned
short
0x06 0-󹪜󹪜h W
Appendix
A.1Modbus
PAC4220
Equipment Manual, L1V30827278B-01 133