5.5 Applying the measuring current
The device is designed f
or connection of current transformers with secondary currents of 1A
and 5A. It is only possible to measure alternating currents.
The current measuring inputs can each be loaded with 10A continuously or with 100A for 1
second.
DANGER
Open transformer circuits will result in electric shock and arc ash hazards
W
ill cause death, serious injury or property damage.
It is only possible to measure the current with external current transformers.
• Do not use fuses for circuit protection.
• Do not open the secondary circuit of the current transformers under load.
• Short circuit the secondary current terminals of the current transformer before removing
this device.
• The safety information for the current transformers used must be followed.
NOTICE
Alternating current measurement only, otherwise the device will become non-functional
Use the de
vice to measure alternating current only.
Direction of current ow
Please t
ake account of the direction of current ow when connecting the current measuring
inputs. With inverse connection, the measured values are inverted and receive a negative sign.
To correct the direction of current ow, it is not necessary to reverse the input terminals.
Instead, change the interpretation of the direction in the device settings.
You will nd information about device settings in the Basic parameters (Page81) section.
See also
Safety information (Page43)
Measuring inputs (Page21)
Commissioning
5.5Applying the measuring current
PAC4220
Equipment Manual, L1V30827278B-01 63