EasyManua.ls Logo

Siemens SICAM Q100 - Page 203

Siemens SICAM Q100
376 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8 Operation at Use of a PC
8.3 Configuration of the Device
203SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018
8.3.7.4.3 Mapping – Indications
At Indications, the indications are defined which are read by a selected Modbus slave device.
Default Settings and Settings of the Modbus Slave Device 1
Table 8-27 Settings for assignment of the indications of the Modbus slave device 1
Parameter Default Setting Setting Range
Name Indication x Slv 1
(x = 1 to 6)
Max. 31 characters
Register type -none- -none-
Coil status registers
Input status registers
Input registers
Holding registers
For -none-, the assignment is ignored
and the corresponding indication cannot
be selected for other functions.
Data format on bus
(see also Table 8-28.)
1 Bit 1 Bit
1 Bit in UInt32
Register number 1 1 to 65 535
Bit offset
(only relevant for register types
Input register or Holding register)
0 0 to 15 (for Data format 1 Bit)
0 to 31 (for Data format 1 Bit in UInt32)
Table 8-28 Data format on Bus
Data Format
on Bus
Description Setting
Range
Invalid
recognition
Used by (example)
1 Bit 1 bit (for all register types; addi-
tionall select Bit offset for Input
register and Holding register)
0 = of
1 = on
none SICAM P50 7KG775,
SENTRON 3WL/3VL,
SIPROTEC4
1 Bit in UInt32 1 bit in 2 successive Input regis-
ters or Holding registers which
have to be read together.
0 = of
1 = on
none SENTRON PAC3x00

Table of Contents

Other manuals for Siemens SICAM Q100

Related product manuals