Configuring with Web Based Management
4.4 "System" menu
SCALANCE SC-600 Web Based Management (WBM)
196 Configuration Manual, 10/2021, C79000-G8976-C475-03
The following columns are only relevant for "NTP (secure)". Otherwise, these boxes
cannot be edited:
Key ID
Enter the ID of the authentication key.
Hash Algorithm
Specify the format for the authentication key.
Key
Enter the authentication key. The length depends on the hash algorithm.
The following minimum lengths are recommended for the hash algorithm:
DES: ASCII 8 characters
MD5: ASCII 16 characters
SHA1: ASCII 20 characters
Key Confirmation
Enter the authentication key for confirmation.
4.4.11 Auto logout
Setting the automatic logout
On this page, set the times after which there is an automatic logout from WBM or the
CLI following user in activity.
If you have been logged out automatically, you will need to log in again.
Procedure
1. Enter a value of 60-3600 seconds in the "Web Base Management (s)" input box. If you
enter the value 0, the automatic logout is disabled.
2. Enter a value of 60-600 seconds in the "CLI (SSH, Serial) (s)" input box. If you enter the
value 0, the automatic logout is disabled.
3. Click the "Set Values" button.