The following information and buttons can be seen (from left to right) in the detail view:
1. Overview line:
PCS 7 group displays: Alarm, warning, step error, operator prompt
The operator prompt icon is also displayed here if one of the following views is shown:
Lock/Unlock Messages
Message acknowledgement
Message suppression
Batch allocation
Indicates whether the associated SFC of the faceplate is allocated:
No icon Associated SFC is not allocated.
Associated SFC of an EPH/EOP has been allocated to SIMATIC BATCH.
Associated SFC of an equipment module (EM) is allocated by an equipment
phase (EPH).
Context of the SFC associated with faceplate:
No icon Neutral SFC
Associated SFC is a sequential control for an equipment module (EM).
Associated SFC is a sequential control for an equipment phase (EPH).
Associated SFC is a sequential control for an equipment operation (EOP).
View selection
2. Control and display section of the SFC:
In the fields of the first row:
Status display and SFC operating status label
Status display and name of the active sequencer
Status display and name of the held sequencer
Box with drop-down list for displaying and changing the switching modes
In the fields of the second row:
The current operating mode (MANUAL/AUTO)
"Continuous mode" status flag for bumpless changeover, for example, when restarting
an SFC to avoid having to switch it off first. Display if output QCONT = 1.
Operating and monitoring SFCs
6.5 "SFC Instance" faceplate, "Actual Values" view
SFC Visualization (V9.0)
38 Programming and Operating Manual, 05/2017, A5E41356392-AA