6.14 PCS 7 SFC Control
PCS 7 SFC Control
The following current information is displayed:
Heading
● Name of the assigned SFC (chart or instance name) *)
1st Row
● Mode (MANUAL / AUTO)
● Abbreviation for the step control mode
("T", "T or O", "T and O", "O", "T / T and O").
● SFC status (chart or instance);
You will find more information in: Icons for Operating States (Page 95).
● Status in the CPU
CPU stop
CPU start with consistent data
CPU start with inconsistent data
● Group display for step error (if it exists, otherwise empty).
● Group display for operator prompt (if it exists, otherwise empty).
2nd Row
● Name of the active sequencer
3rd Row
● Operating state of the active sequencer;
You can find more detailed information in the section: Icons for Operating
States (Page 95).
● Display for step error "S" (if it exists, otherwise empty).
● Display for operator prompt "O" (if it exists, otherwise empty).
4th Row
● Step: Name of the first **) active step.
5th Row
● Runtime: Current runtime of the first **) active step.
● Button for the SFC display: "Overview" or "Section" or "Faceplate".
*) If ## Initialization error ## is displayed instead of the name of the text, this SFC control is assigned
to an SFC that has been deleted in WinCC.
If the SFC still exists in the AS project, recompile the OS to transfer the SFC back to WinCC data
management. Otherwise, you assign another SFC chart to the SFC control.
**) Several steps can be active at the same time in a simultaneous sequencer.
Operating and monitoring SFCs
6.14 PCS 7 SFC Control
SFC Visualization (V9.0)
Programming and Operating Manual, 05/2017, A5E41356392-AA 51