Command Buttons
Buttons for filter settings appear in the column headings. You can open and close the filter
dialog box by clicking on this icon:
The following filter settings are available for selection:
SFC: Operating status and SFC display
Group display: Message class displays
Operating mode
Step control mode: Step Control Modes
Step error: Step error on/off
CPU: Stop and restart
IE: Interconnection error on/off
OE: Operator error on/off
The filter is not available for all columns.
To move a selected row up or down one row at a time, click one of the following buttons:
Up
Down
Once selected, you can use commands to control an SFC. The following buttons are available
for this:
Start or Resume
Abort
Hold
Restart
You open a selected SFC with the "Section" or "Overview" buttons in the selected display.
Note on the Display
If a line containing only the SFC name is shown in light gray in the SFC multichart control,
then this SFC is no longer in the WinCC data management. It is deleted here and was not
transferred during the most recent OS compilation.
Tip: If the SFC still exists in the AS project, recompile the OS to transfer the SFC back to
WinCC data management. Otherwise, you have to assign another SFC to the line in the
SFC multichart control or delete the line.
Line selections are discarded after approximately 30 seconds.
Operating and monitoring SFCs
6.15 PCS 7 SFC MultiChart Control
SFC Visualization (V9.0)
Programming and Operating Manual, 05/2017, A5E41356392-AA 55