Configuration
4.18 Data points
CP 1243-8 IRC
Operating Instructions, 02/2018, C79000-G8976-C385-03
161
l-
DNP3: 0 ... 255
ST7 and IEC: Fixed assignment with "1"
Monitors the number of pulses sent by the master (Count). If the number of
pulses received from the master exceeds the value configured here, the
command is discarded.
If 0 (zero) is set, the monitoring is disabled.
l-
Monitors the pulse duration transmitted by the master with the command
(On
-time).
If the pulse duration sent by the master exceeds the value configure
d here,
the command is discarded by the communication module if no "Pulse dur
a-
tion replacement time" has been configured.
When the "Max. pulse duration" is exceeded and "Pulse duration replac
e-
ment time" is configured, the pulse duration sent by the master
is checked
for the "Pulse duration replacement time".
If the value is 0 (zero), no "Max. pulse duration" is checked.
Pulse duration replacement time (s)
l-
Replacement value for the
pulse duration If the pulse duration received from
the master exceeds the value configured in “Max pulse duration“.
If the value is 0 (zero), no replacement value is used.
If the ""Max. pulse duration" and "Pulse duration replacement time" are both
configured with zero, each command is discarded.
l-