Configuration
4.9 Serial interface
CP 1243-8 IRC
88 Operating Instructions, 02/2018, C79000-G8976-C385-03
AT initialization
User-defined
If the option is enabled the AT initialization string for the basic settings of the modem can
be assigned manually.
If the option is disabled, the AT initialization string is preset for the specific modem:
MD3 : ATS45=3\N0F0&W
MD4 : ATS45=83$P1\N0&W
MD720 : For information on the initialization string, refer to the manual /8/ (Page 227).
AT string
Input box for the AT initialization string
Transmission setting for conditionally spontaneous frames
Transmission criterion
Only for interfaces with the Network node type "Station" / "Node station".
The transmission criterion controls connection establishment for the transmission of
conditional spontaneous frames. This reduces the number of connection retries.
Range of values:
Standard conditions
No connection will be established due to the existence of conditional spontaneous
frames.
Only in the following cases will a connection be established to send conditional
spontaneous frames.
- Threatened overflow of the send buffer
- Connection establishment by the communications partner
Degree of filling
The CP only establishes a connection when the configured fill level of the send buffer
for conditional spontaneous frames is exceeded.
In the input box, enter the fill level (%) of the send buffer at which when exceeded the
CP establishes a connection.
Time
The CP sends conditional spontaneous frames at a time of day, configurable with
"Hours" / "Minutes".
Time scheme
The CP sends the conditional spontaneous frames cyclically at an interval,
configurable with "Hours" / "Minutes".

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC S7-1200 CP 1243-8 IRC and is the answer not in the manual?

Siemens SIMATIC S7-1200 CP 1243-8 IRC Specifications

General IconGeneral
Product TypeCommunication Processor
SeriesSIMATIC S7-1200
ModelCP 1243-8 IRC
Data Transfer Rate10/100 Mbps
Power Supply24 V DC
MountingDIN rail
Dimensions (W x H x D)45 mm x 100 mm x 75 mm
Digital Inputs Quantity0
Digital Outputs Quantity0
Supported ProtocolsISO-on-TCP
InterfaceEthernet
IP AddressingStatic, DHCP
ConfigurationSTEP 7 Basic/Professional
Operating Temperature-20°C to +60°C
WeightApprox. 200 g