Configuration
4.9 Serial interface
CP 1243-8 IRC
Operating Instructions, 02/2018, C79000-G8976-C385-03
89
Time options
Call acceptance delay
Wait time (s) before accepting an incoming call
The wait time makes it possible for the CP to accept the call when a telephone is
connected parallel to the CP on a shared telephone connector.
Default setting: 0. Permitted range: 0...30
Dial test interval
The test interval (min) is started when no connection could be established by the CP after
3 attempted repetitions. When the test interval elapses, the CP re-establishes the
connection.
If the connection establishment fails, on the other hand, the test interval is restarted.
Default setting: 5. Permitted range: 0...255
Minimum connection duration
Only for interfaces with the Network node type "Master station".
Minimum connection duration (s) for a dial-up connection.
The minimum connection duration may be required in fast dial-up networks to be able to
wait for the reply during a general request before the connection is terminated.
Default setting: 5. Permitted range: 0...65535
Abort delay time
Duration (s) a dial-up connection is retained when the send buffer of the CP is full and the
CP can forward no further frames or data to the CPU.
During the abort delay time, received frames are acknowledged negatively and the
communications partner repeats sent and negatively acknowledged frames.
When the abort delay time elapses, the connection is terminated.
Default setting: 20. Permitted range: 0...255
Event transmission
Type of transmission
Specifies the form in which data frames are sent.
As single frames
Several frames as a block
Mobile wireless settings
PIN
PIN of the SIM card of the modem MD720

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC S7-1200 CP 1243-8 IRC and is the answer not in the manual?

Siemens SIMATIC S7-1200 CP 1243-8 IRC Specifications

General IconGeneral
Product TypeCommunication Processor
SeriesSIMATIC S7-1200
ModelCP 1243-8 IRC
Data Transfer Rate10/100 Mbps
Power Supply24 V DC
MountingDIN rail
Dimensions (W x H x D)45 mm x 100 mm x 75 mm
Digital Inputs Quantity0
Digital Outputs Quantity0
Supported ProtocolsISO-on-TCP
InterfaceEthernet
IP AddressingStatic, DHCP
ConfigurationSTEP 7 Basic/Professional
Operating Temperature-20°C to +60°C
WeightApprox. 200 g