Application planning
5.2 System and load power supply
Automation system
System Manual, 01/2023, A5E03461182-AK
119
Connection, structure and configuration of an S7-1500 with PS 60W 24/48/60VDC HF
You must insert the system power supply PS 60W 24/48/60VDC HF in slot 0.
Figure 5-9 Slot PS 60W 24/48/60VDC HF
If you are using the PS 60W 24/48/60VDC HF, the 24 V supply of the CPU is not taken into
account in the power budget calculation.
Note
You may only connect the 24
V
DC supply voltage directly to the system power supply and
not to the CPU.
You must set the "System power supply" parameter to the option "No connection to supply
voltage L+" during configuration of the CPU. STEP 7 checks the setting when compiling
the configuration.
Figure 5-10 Connecting PS 60W 24/48/60VDC HF