Flexible automation concepts
11.2 Configuration control (option handling)
Automation system
244 System Manual, 01/2023, A5E03461182-AK
11.2.2.1 Control data record for the S7-1500 Automation System
Slot assignment
The following table shows the slot assignment of the modules for the S7-1500 automation
system:
Table 11- 2 Slot assignment
System power supply (optional)
I/O modules/system power supplies, depending on
the station option
Control data record
For configuration control of the S7-1500 automation system, you define a control data record
196 V4.0, which contains a slot assignment. The table below shows the structure of a control
data record with explanations of the individual elements.
Table 11- 3 Configuration control: Structure of control data record 196
Header
Slot 0 of the station master
Slot assignment in the
station option
Contains information on which module is
inserted in which slot.
The following rule determines which
value you must enter in the respective
byte:
• If the module is included in the station
option, enter the slot number of the
module.
• If the module is not included in the
station option, enter 255.
Slot 1 of the station master
station option
(always 1, because the CPU
Slot 2 of the station master
Slot assignment in the
station option
Slot 3 of the station master
Slot assignment in the
station option
4 + (max. slot num-
Maximum slot of the sta-
Slot assignment in the