Commissioning
12.4 Procedure for commissioning the ET 200MP distributed I/O system
Automation system
262 System Manual, 01/2023, A5E03461182-AK
12.4 Procedure for commissioning the
ET 200MP distributed I/O system
12.4.1 Commissioning the ET 200MP for PROFINET IO
Introduction
The commissioning of your automation system depends on the plant configuration.
Commissioning procedure
To commission the ET 200MP as IO device for PROFINET IO, proceed as follows:
Table 12- 2 Procedure for commissioning the ET 200MP as an IO device for PROFINET IO
Step
Procedure
See...
1
Install ET 200MP
Section Installation (Page 125)
2 Connect ET 200MP
Supply voltages
PROFINET IO
Sensors and actuators
Section Wiring (Page 148)
4
Configure IO controller
CPU manual or documentation of the IO controller
5
Switch on supply voltages for the
IO controller
CPU manual or documentation of the IO controller
6
Switch on supply voltages for
IO devices
Interface module
(https://support.automation.siemens.com/WW/view/en/6
7295970/133300) manual
7
Download configuration to the
IO controller
STEP 7 online help
8
Switch IO controller to RUN mode
CPU manual or documentation of the IO controller
9
Check LEDs
Interface module
(https://support.automation.siemens.com/WW/view/en/6
7295970/133300) manual
10
Test inputs and outputs
The following functions are helpful: Monitoring and
modifying tags, testing with program status, forcing,
modifying the outputs. See section Test and service func-
tions (Page 328)
Note
The operating mode transitions for the IO controller from RUN to STOP or from STOP to RUN
can take several milliseconds, until the mode transition for the inputs and outputs of all
I/O modules for the ET
200MP station is completed. This delay also applies to isochronous
mode.