Commissioning
12.9 Identification and maintenance data
Automation system
System Manual, 01/2023, A5E03461182-AK
285
12.9.2 Record structure for I&M data
Reading I&M records via user program (centrally and distributed via PROFINET IO)
Use Read data record ("RDREC" instruction) to access specific identification data. Under the
associated record index you obtain the corresponding part of the identification data.
The records are structured as follows:
Table 12- 6 Basic structure of data records with I&M identification data
BlockType 2 I&M0: 0020H
I&M1: 0021
H
I&M2: 0022
H
BlockLength 2 I&M0: 0038H
I&M1: 0038
H
I&M2: 0012
H
(see table below)
H
I&M1/Index AFF1H: 54
I&M2/Index AFF2
H: 16
-
-
Table 12- 7 Record structure for I&M identification data
Identification data 0: (record index AFF0H)
Vendor name
(002A
H = SIEMENS AG)
Article number of the module
(e.g. CPU 1516-3 PN/DP)
Serial number (device-specific)
IM_HARDWARE_REVISION read (2 bytes) 1 corresponds to hardware version
Provides information about the firmware
version of the module (e.g. V1.0.0)
• SWRevisionPrefix
• IM_SWRevision_Functional_E
nhancement
(1 byte) 0000
H - 00FFH
• IM_SWRevision_Bug_Fix
H
H
• IM_SWRevision_Internal_
Change
(1 byte) 0000
H - 00FFH