Flexible automation concepts
11.2 Configuration control (option handling)
Automation system
System Manual, 01/2023, A5E03461182-AK
247
Note
The data in the feedback data record is always mapped for all modules. In a Shared Device
configuration, it is therefore irrelevant which IO controller the respective modules are
assigned to.
As long as no control data record was sent, a one
-to-one module assignment is assumed for
the compilation of data record 197 (station master station option).
Error messages
In the case of an error when reading the feedback data record, the RDREC instruction returns
the following error messages via the STATUS block parameter:
Table 11- 8 Error messages
Error code
Meaning
80B1H
Invalid length; the length information in data record 197 is not correct.
80B5
H
Configuration control not configured
80B8
H
Parameter error
The following events cause a parameter error:
Incorrect block ID in the header (not equal to 197)
Invalid version identifier in the header
A reserved bit was set
Multiple slots in the station master are assigned to the same slot in the station
option
11.2.2.4 Examples of configuration control
A station master consisting of a system power supply, CPU, and three I/O modules is
configured in STEP 7 in the following section.
The module at slot 3 is not present in the station option 1 and is "hidden" by the
configuration control.
In station option 2, the order of the modules in slots 3 and 4 is interchanged. The modified
order of the modules is made known to the CPU by a modified control data record.