Commissioning
12.3 Procedure for commissioning the S7-1500 automation system
Automation system
System Manual, 01/2023, A5E03461182-AK
261
12.3.2 First power-on of the CPU
Requirements
An S7-1500 automation system has been installed.
The system has been wired.
The SIMATIC Memory Card is inserted in the CPU.
Procedure
Proceed as follows to commission the CPU:
Switch on the system power supply and load current supply.
Result:
The CPU executes a flash test:
All LEDs flash at 2 Hz
RUN/STOP LED flashes alternately yellow/green
ERROR LED flashes red
MAINT LED flashes yellow
The CPU performs the system initialization and evaluates the SIMATIC Memory Card:
RUN/STOP LED flashes yellow at 2 Hz
After the system initialization has been completed, the CPU goes to STOP mode:
The RUN/STOP LED lights up yellow