EasyManua.ls Logo

Siemens Simatic S7-1500 / ET 200MP - Analog Input Modules

Siemens Simatic S7-1500 / ET 200MP
385 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
System overview
4.6 Input and output modules
Automation system
76 System Manual, 01/2023, A5E03461182-AK
4.6.5 Analog input modules
Analog input modules and analog input/output module
Short designation AI 8xU/I HF
AI 8xU/I HS
AI 8xU/R/RTD/TC HF
AI 8xU/I/RTD/TC ST
AI 4xU/I/RTD/TC ST
AI 8xU/I/R/RTD BA
AI 4xU/I/RTD/TC / AQ
2xU/I ST
Article number
High Feature (HF)
6ES7531-7NF00-0AB0
6ES7531-7PF00-0AB0
---
---
High Speed (HS)
6ES7531-7NF10-0AB0
---
---
---
Standard (ST)
---
6ES7531-7KF00-0AB0
6ES7531-7QD00-0AB0
6ES7534- 7QE00-0AB0
Basic (BA)
---
---
6ES7 531-7QF00-0AB0
---
Manual
High Feature (HF)
Link
Link
---
---
High Speed (HS)
Link
---
---
---
Standard (ST)
---
Link
Link
Link
Basic (BA)
---
---
Link
---
Width
35 mm
35 mm
25 mm
25 mm
Number of inputs
8
8
4
4
Resolution
16 bits including sign
16 bits including sign
16 bits including sign
16 bits including sign
Measurement type
Voltage, current
Voltage, current, re-
sistance, thermal resis-
tor, thermocouple
Voltage, current, re-
sistance, resistance
thermometer, thermo-
couple
Voltage, current, re-
sistance, thermal resis-
tor, thermocouple
Electrical isolation
between channels
Only with HF
Only with HF
---
---
Number of potential
groups
1
1
---
---
Rated supply voltage
24 V DC
24 V DC
24 V DC
24 V DC
Permissible potential
difference between
inputs (UCM)
HF: 60 V DC / 30 V AC
HS: 10 V DC
HF: 60 V DC / 30 V AC
ST: 10 V DC
20 V DC 20 V DC
Diagnostic interrupt
X
X
X
X
Hardware interrupt
X
Two high limits and
two low limits in each
case
X
Two high limits and
two low limits in each
case
X
Two high limits and
two low limits in each
case
X
Two high limits and
two low limits in each
case
Isochronous mode
Only HS
---
---
---
Conversion time (per
channel)
HF: Fast mode:
4/18/22/102 ms;
Standard mode:
9/52/62/302 ms
HS: 62.5 µs, per mod-
ule, regardless of
number of activated
channels
HF: Fast mode:
4/18/22/102 ms;
Standard mode:
9/52/62/302 ms
ST: 9/23/27/107 ms
9/23/27/107 ms
9/23/27/107 ms
Calibration in RUN
mode
Only with HF
Only with HF
X
X
Oversampling
Only with HS
---
---
---

Table of Contents