Installation
6.3 Installing the standard rail adapter
Automation system
132 System Manual, 01/2023, A5E03461182-AK
6.3 Installing the standard rail adapter
Introduction
The DIN rail adapter allows you to mount the SIMATIC S7-1500/ET 200MP automation system
on the standard 35 mm mounting rails.
You order the DIN rail adapter as separate accessories.
Note
Note the following reduced technical specifications regarding mechanical load when
you install the S7
-1500/ET 200MP modules on the 35 mm DIN rail using the DIN rail
adapter:
Vibration test acc. to IEC
60068-2-6 (sinusoidal)
5 Hz f 8.4 Hz, constant amplitude 3.5 mm
8.4 Hz f 150 Hz, constant acceleration 1 g
Duration of vibration: 10 frequency sweeps per axis in each of three perpendicular axes
Shock, tested according to IEC
60068-2-27
Type of shock: Half-sine
Shock intensity: 150 m/s
2
peak value, 11 ms duration
Direction of shock: 3 shocks each in (+/-) direction, along each of the 3 mutually
perpendicular axes
Article number
6ES7590-6AA00-0AA0
The scope of delivery consists of ten adapters, ten hexagon socket-head screws and ten