12.3 Procedure for commissioning the S7-1500 automation system
Automation system
System Manual, 01/2023, A5E03461182-AK
257
System power supply or load current supply
Are all system power supplies and load current supplies switched off?
Is the power cable connector correctly wired?
Has the connection to line voltage been made?
12.3 Procedure for commissioning the S7-1500 automation system
Requirements
The CPU is in the "Factory settings" state or has been reset to factory settings. You can find
more information in the section Resetting the CPU to factory settings (Page 319).
The SIMATIC memory card is as delivered or has been formatted.
Commissioning procedure
For the first commissioning of an S7-1500 automation system, we recommend the following
procedure:
Table 12- 1 Procedure for commissioning the SIMATIC S7-1500
Step
Procedure
See...
1
Configure hardware in STEP 7 and perform power balance calcu-
lation (see also "Requirements: CPU as bus device")
Section Power balance calculation
(Page 121)
2
Create user program
STEP 7 online help
3
Insert required modules
Section Installation (Page 125)
4
Wiring and checking the assembly (system power supplies, front
connectors, etc.)
Section Wiring (Page 148)
5
Insert SIMATIC memory card in the CPU
Section Removing/inserting a SIMATIC
memory card on the CPU (Page 258)
6
Switch on the CPU and system power supply
Section First power-on of the CPU
(Page 261)
7 Check LEDs The meaning of the LEDs can be found in
the manuals of the modules.
8
Evaluate information on the CPU's display
Section CPU display (Page 290)
9
Load hardware configuration and user program to the CPU
Online and diagnostics functions in
STEP 7
10
Test inputs and outputs
The following functions are helpful:
Monitoring and modifying tags, testing
with program status, forcing, modifying
the outputs in STOP mode. Section Test
and service functions (Page 328)