Configuring
8.2 Configuring ET 200MP distributed I/O system
Automation system
System Manual, 01/2023, A5E03461182-AK
205
Reference
Additional information on process image partitions is available found in the function manual,
Cycle and response times (https://support.automation.siemens.com/WW/view/en/59193558).
8.2 Configuring ET 200MP distributed I/O system
Introduction
You configure and assign parameters to the ET 200MP (interface module and I/O modules)
with STEP 7 or in the configuration software of another manufacturer.
Requirements
Table 8- 1 Requirements for installation
Configuration software
Requirements
Installation information
STEP 7 as of V13
1)
IM 155-5 PN ST and IM 155-
5 DP ST:
as of firmware version V2.0.0
IM 155-5 PN HF:
as of firmware version V1.0.0
PROFINET:
PROFINET GSD files
(https://support.industry.siemens.c
om/cs/ww/de/view/68189683/en?dl
=en)
PROFIBUS:
PROFIBUS GSD files
(https://support.industry.siemens.c
om/cs/de/de/view/80206700/en?dl
=en)
The TIA Portal supports the following
GSDML specifications:
TIA Portal V11: V2.3
TIA Portal V12SP1: V2.31
TIA Portal V14: V2.32
TIA Portal V15: V2.34
The GSDML versions are largely down-
wards compatible.
The ET 200MP is already delivered with a
GSD file based on specification V2.3. The
GSD file can be installed and used in the
TIA Portal.
STEP 7 online help
STEP 7 V5.5 SP4 HF1 or higher
PROFINET:
PROFINET GSD files
(https://support.automation.sieme
ns.com/WW/view/en/19698639/13
0000)
PROFIBUS:
PROFIBUS GSD files
(https://support.automation.sieme
ns.com/WW/view/en/10805317/13
3300)
STEP 7 online help
Software of another manufactur-
er
Manufacturer documentation
1)
STEP 7 does not support all the PROFINET features contained in the GSDML specifications. Non-supported features can-