Commissioning
12.4 Procedure for commissioning the ET 200MP distributed I/O system
Automation system
System Manual, 01/2023, A5E03461182-AK
263
12.4.2 Commissioning the ET 200MP for PROFIBUS DP
Introduction
The commissioning of your automation system depends on the plant configuration.
Commissioning procedure
To commission the ET 200MP as a DP device on PROFIBUS DP, follow these steps:
Install the ET 200MP (with IM 155-5 DP ST)
Section Installation (Page 125)
2 Set the PROFIBUS address on the interface mod-
ule
Manual for the interface module
(https://support.automation.siemens.com/WW/view/en/779108
3 Connect the ET 200MP
• Supply voltages
• PROFIBUS DP
• Sensors and actuators
Section Wiring (Page 148)
Configure DP master (including PROFIBUS ad-
dress)
Documentation of the DP master
Switch on supply voltages for DP master
Documentation of the DP master
Switch on supply voltages for DP devices
(https://support.automation.siemens.com/WW/view/en/779108
Download configuration to the DP master
Documentation of the DP master
(https://support.automation.siemens.com/WW/view/en/779108
The following functions are helpful: Monitoring and modifying
tags, testing with program status, forcing, modifying the out-
puts.
Section Test and service functions (Page 328)
During operating mode transitions of the DP master from RUN to STOP or from STOP to RUN,
it can take several milliseconds until the mode transition is complete for the inputs and
outputs of all the I/O modules of the ET 200MP.