Maintenance
14.6 Reset to factory settings
Automation system
324 System Manual, 01/2023, A5E03461182-AK
Reference
More information on "Reset to factory settings" can be found in the Function Manual
Structure and use of the CPU memory
(https://support.automation.siemens.com/WW/view/en/59193101) in the section on memory
areas and retentivity, and in the online help for STEP 7. For information on the memory reset
of the CPU, refer to the section CPU memory reset (Page 271).
14.6.2 Resetting interface module (PROFINET IO) to factory settings
Introduction
The interface module can be reset to its factory state using "Reset to factory settings".
Method of resetting an interface module to factory settings
Via STEP 7 (online via PROFINET IO)
Procedure using STEP 7
To reset an interface module to factory settings via STEP 7, follow these steps:
Make sure that an online connection to the interface module exists.
1. Open the online and diagnostics view of the interface module.
2. In the "Functions" folder, select the "Reset to factory settings" group.
3. Click the "Reset" button.
4. Click "OK" in response to the confirmation prompts.
Result: The interface module then performs a "Reset to factory settings".
Result after resetting to factory settings
Table 14- 3 Properties of the interface module when shipped
Properties
Value
Parameter
Default setting
IP address
Not present
Device name
Not present
MAC address
Present
I&M data
Identification data (I&M0) present
Maintenance data (I&M1, 2, 3) reset
Firmware version
Present