EasyManua.ls Logo

Siemens Simatic S7-1500 / ET 200MP - Data Record 100 Validation Error Codes

Siemens Simatic S7-1500 / ET 200MP
385 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
System overview
4.5 Interface modules for SIMATIC S7-1500 I/O devices
Automation system
System Manual, 01/2023, A5E03461182-AK
67
Additional information
You can find a detailed description of the "Trace" function in the Function Manual
SIMATIC/SINAMICS Using the trace and logic analyzer function SIMATIC/SINAMICS Trace and
logic analyzer function (https://support.industry.siemens.com/cs/ww/en/view/64897128).
4.5 Interface modules for SIMATIC S7-1500 I/O devices
An interface module connects the SIMATIC S7-1500 I/O devices as ET 200MP distributed I/O
system via PROFINET or PROFIBUS with the controller. The interface module exchanges the
data between the higher-level controller and the I/O modules.
Interface modules
Short designation IM 155-5 PN HF
IM 155-5 PN ST
IM 155-5 PN BA IM 155-5 DP ST
Article number
High Feature (HF)
6ES7155-5AA00-0AC0
---
---
Standard (ST)
6ES7155-5AA01-0AB0
---
6ES7155-5BA00-0AB0
Basic (BA)
---
6ES7155-5AA00-0AA0
---
Manual
High Feature (HF)
Link
---
---
Standard (ST)
Link
---
Link
Basic (BA)
---
Link
---
Supply voltage
24 V DC
24 V DC
24 V DC
Number of IO modules
30
12
12
Interfaces 1 x PROFINET IO; integrated 2-
port switch
1 x PROFINET IO; integrated
2-port switch
1 x PROFIBUS
Min. slave interval
---
---
100 μs
Isochronous real-time commu-
nication (IRT)
X
---
---
Isochronous mode
X (shortest cycle 250 µs)
---
---
Prioritized startup
X
---
---
Device replacement without
programming device
X (LLDP; address assignment
by a tool, for example, STEP 7)
X (LLDP; address assignment
by a tool, for example, STEP
7)
---
Shared device
High Feature: 4 IO controllers
Default: 2 IO controllers
2 IO controllers
---
Identification and mainte-
nance data
I&M 0 to 3
I&M 0 to 3
I&M 0 to 3
Media redundancy (MRP)
X
X
---
Media redundancy with
planned duplication (MRPD)
High Feature: X
Default:
--- ---
System redundancy on S7-
400H
High Feature: With GSD file
and STEP 7 V5.5 SP3 or higher
Default:
---
---

Table of Contents

Other manuals for Siemens Simatic S7-1500 / ET 200MP

Related product manuals