Wiring
7.6 Connecting the supply voltage
Automation system
System Manual, 01/2023, A5E03461182-AK
167
7.6 Connecting the supply voltage
Introduction
The supply voltage of the CPU/interface module is supplied by means of a 4-pole connection
plug, which is located on the front or below on the CPU / interface module.
Connection for supply voltage (X80)
The connections of the 4-pole connector have the following meaning:
+24 V DC of the supply voltage (current limited to 10 A)
Ground of the supply voltage (current limited to 10 A)
Ground of the supply voltage for loop-through
+24 V DC of the supply voltage for loop-through
Spring opener (one spring opener per terminal)
Figure 7-5 Connection for supply voltage
The cable connector offers you the option of looping the supply voltage uninterrupted, even
when it is unplugged.
For the maximum wire cross-sections, observe the information in the tables of the Wiring
rules (Page 162).
Requirements
Only wire the cable connector when the supply voltage is turned off.
Observe the Wiring rules (Page 162).
Tools required
3 to 3.5 mm screwdriver
Tool-free connection of cables: multi-wire (stranded), with end sleeve or ultrasonic compressed
To connect a wire without tools, follow these steps:
1. Strip 8 to 11 mm of the wires.
2. Seal or crimp the wire with end sleeves.
3. Insert the wire into the push-in terminal as far as it will go.
4. Push the wired connector into the socket of the CPU/interface module.