Wiring
7.5 Wiring rules
Automation system
162 System Manual, 01/2023, A5E03461182-AK
7.5 Wiring rules
Introduction
Use suitable cables for connecting the S7-1500 automation system/ET 200MP distributed I/O
system. Also select the cable insulation corresponding to the applied voltage. The following
tables present the wiring rules for the CPU, interface module, system power supply, load
current supply, front connector and power supply elements.
CPU, interface module, system power supply and load current supply
Table 7- 2 Wiring rules for CPU, interface module, system power supply and load current supply
Wiring rules for ... CPU/interface module System power and load cur-
rent supply
Permitted cable cross-sections of solid cables (Cu)
-
-
-
-
Permitted cable cross-
sections of flexible cables
(Cu)
Without wire end
sleeve
0.25 to 2.5 mm
2
0.5 to 2.5 mm
2
AWG
*
: 24 to 14
AWG
*
: 20 to 14
With end sleeve
0.25 to 1.5 mm
2
0.5 to 1.5 mm
2
AWG
*
: 24 to 16
AWG
*
: 20 to 16
Number of wires per connection
1
1
Stripped length of the wires
10 to 11 mm
7 to 8 mm
End sleeves according to
DIN 46228
without plastic sleeve
Design A, 10 mm long
Design A, 7 mm long
with plastic sleeve 0.25
to 1.5 mm
2
Design E, 10 mm long
Design A, 7 mm long
Sheath diameter
-
8.5 mm
Tool
3 to 3.5 mm screwdriver, conic
design
3 to 3.5 mm screwdriver, conic
design
Connection system
Push-in terminal
Screw terminal
Tightening torque
-
from 0.5 Nm to 0.6 Nm
* American Wire Gauge